About calibration: 1 If the collected temperature error exceeds 1%, it can be calibrated. 2 Calibration is not recommended if the error does not exceed 0.5%. 3. If the calibration causes a larger error, please short the RES jumper for 5 seconds to restore the factory settings, and then recalibrate. How to calibrate the voltage value of PTDNC04: The temperature value is in register 0x0000-0x0003 (0-3), and the calibration value is in register 0x0040-0x0043 (64-67) It is recommended to calibrate the three temperature values ​​of high, medium and low at the same time. For example, -40-220℃ PT100 version: It is recommended to calibrate these three values: 10℃/100℃/200℃